6
Main control board connections (cont.)
J23 Wire terminal connection provides optically
isolated connection to air flow proving switch
and safety circuit. Terminal 12 supplies 24 VAC
to proving switch circuit, SPST, which closes
when air flow is present. Terminal 13 is the
return connection from the proving switch into
the VAPOR-LOGIC
®
3
control. Terminal 14
supplies 24 VAC to safety circuit, SPST, which
is closed under normal operating conditions.
Terminal 15 is the return connection from the
safety circuit into the VAPOR-LOGIC
3
control.
J25 Wire terminal connector provides input for RTD
tank temperature sensor. Terminal 19 supplies 21
VDC to temperature sensor. Terminal 20 is the
return connection from the temperature sensor
into the VAPOR-LOGIC
3
control. Terminal 18
has no connection.
J26 Wire terminal connector receives the necessary
signal from the controlling RH sensor.
• Terminal 21: Positive polarity 21 VDC supply
(25 mA max)
• Terminal 22: Control signal
• Terminal 23: Signal ground
• Input selector pin J17 configures J26 input
Product overview
Main control board connections (cont.).
Product overview:
Main control board connections
J27 Wire terminal connector receives the necessary
signal from the duct high limit RH sensor.
• Terminal 24: Positive polarity 21 VDC supply
(25 mA max)
• Terminal 25: Control signal
• Terminal 26: Signal ground
• Input selector pin J18 configures J27 input
J28 Wire terminal connector receives the necessary
signal from the window temperature sensor.
• Terminal 27: Positive polarity 21 VDC supply
(25 mA max)
• Terminal 28: Control signal
• Terminal 29: Signal ground
• Input selector pin J19 configures J28 input