Installation
Wiring VAV sensing device.
Variable air volume (VAV) option
This option is identified as a “V” in the third-from-last
place of your program code nomenclature (for
example: EV11400285A7VOX).
When the VAV control option is requested we provide
a duct mounted humidity transmitter (4-20 mA output
over 0-100% RH range). Install using shielded cable
(see Figure 21-1 below).
The modulating high limit transmitter signal operates
in conjunction with the room or duct controlling
transmitter signal through the VAPOR-LOGIC
®
3
control system to prevent over humidification in the
duct work. VAPOR-LOGIC
3
will start lowering the
humidifier output when the duct relative humidity is
within six percent of the duct high limit set point.
Figure 21-1: Shielded cable
NOTE: Ground shield at control panel end only.
Do not ground shield at device end.
When this occurs, the keypad/display will show the
message “VAV output limit.” If necessary, the
reduction of the humidifier output will continue until
maximum high limit set point has been reached,
shutting off the humidifier completely.
When the high relative humidity starts to decrease in
the duct, VAPOR-LOGIC
3
will slowly start to
increase the production of steam vapor. When the
duct relative humidity decreases to a point greater
than six percent below the duct high limit set point,
the control transmitter will be restored as the primary
controller and the keypad/display will no longer
show the “VAV output limit” text, returning the
control system to normal operation.
Installation:
Wiring VAV sensing device
OM-VL3-18