Main control board connections (cont.)
Important note about J17, J18 and J19:
All connection diagrams show connector shunts
on J17, J18 and J19. The connector shunts and
appropriate software have been selected by
DRI-STEEM based on original customer orders.
Field changing the input connector shunts will
require control input modification: See Page
23 “Changing Control Input.”
J17 Jumper pins determine the configuration of the
type of input control into the RH sensor input
(terminals 21 through 23) for wire terminal
connector J26.
R = Resistance, 0-150 ohms range
Used with on-off humidistats, staging
switches, PE switches
Used with analog 0-150 ohm input device
(pneumatic transducer or humidistat)
I = Milliamp, 0-20 mA range
Used with any humidity sensor with
4-20 mA output
Used with any computer or energy
management system with 4-20 mA output
Internal resistance 249 ohms, terminal 22
proportional signal, terminal 23 signal
ground
V = Volts DC, 0-15 volt range
Used with any control humidistat 0-15V DC
Terminal 21 provides positive 21 VDC
supply, terminal 22 proportional signal,
terminal 23 signal ground
Product overview
Main control board connections (cont.).
Product overview:
Main control board connections
J18 Identical to J17 input selector pins except used
to configure duct high limit RH input (terminals
24 through 26) for wire connector terminal J27
J19 Identical to J17 input selector pins except used
to configure window temperature sensor input
(terminals 27 through 29) for wire connector
terminal J28
J20 Wire terminal connector supplies 24 VAC
voltage via terminals 1 and 2 to the fill valve
and via terminals 3 and 4 to the drain valve.
J21 Wire terminal connector supplies 24 VAC
voltage via terminals 5 and 6 to the power
contactor and via terminals 7 and 8 to the SDU
relay.
J22 Wire terminal connection allows for remote
fault indication. Relay closure is provided
(1 amp max.).