number
Problem Possible cause Action
System may not have
automatic drain
system
Drain fault, plugged
drain valve or plugged
drain pipe
Malfunctioning
autodrain sequence
No power to
automatic drain valve
Defective automatic
drain valve
Inspect unit to verify that automatic
drain valve was furnished.
Clean drain valve piping.
Check VAPOR-LOGIC
®
3
main menu
settings and reset if necessary.
Check if 24 VAC is present at
VAPOR-LOGIC
3
control board
terminals 3 and 4 and drain valve.
Valve should be replaced if voltage is
present at valve and it still does not
open.