DriSteem Vapor-logic3 Instrucciones de operaciones Pagina 59

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 75
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 58
57
Open, shorted, or
incorrect wiring of
humidistat
Signal by others is
incorrect, out of
range, or miswired.
Control signal by
others has exceeded
the range limits.
Open, shorted, or
incorrect wiring of
transmitter
Open, shorted, or
incorrect wiring of
transmitter
Sensor improperly
located
When in the fill
sequence,
VAPOR-LOGIC
3
allows 40 minutes
for the water to reach
the maximum proper
level.
If the water does not
reach the designated
level, and the probe
system is not
satisfied, a fault will
be indicated.
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
Problem
number
Problem Possible cause Action
Humidistat fault
VAV humidity
transmitter fault
Temp comp
transmitter fault
Fill fault
Check wiring terminals
(VAPOR-LOGIC
®
3
terminal J26) for
correct wiring and voltages.
Check wiring terminals
(VAPOR-LOGIC
3
terminal J26) for
correct wiring and voltages.
Correct control signal to 0-20 mA,
0-135 ohms, or 0-15 VDC.
Check wiring terminals
(VAPOR-LOGIC
3
terminal J27) for
correct wiring and voltages.
Check wiring terminals
(VAPOR-LOGIC
3
terminal J28) for
correct wiring and voltages.
Transmitter must be on inside window
glass only.
Check water supply shut-off valve. If it
is closed, open the valve.
Check if the in-line strainer or valves
are plugged. Clean them as needed.
Check if there is 24 VAC present at
control board terminals 1 and 2. If yes,
replace valve.
Verify proper fill valve wiring.
Clean or replace probe.
Verify drain valve is closed.
Verify proper water pressure,
minimum 25 psi.
6
7
8
9
More on next page ...
Vista de pagina 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 74 75