DriSteem Vapor-logic3 Instrucciones de operaciones Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 75
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
2
Summary of features
PID control provides the most accurate,
responsive and adjustable relative humidity
(RH) control.
Self-diagnostic test at start-up
End of season auto-drain
Real-time clock allows time-stamped alarm
tracking, and three ways to program drain and
flush cycles:
1. Usage (after a set number of lbs/kg have
cycled through)
2. Usage and time (set number of lbs/kg plus
defined period of time)
3. Scheduled intervals
Redesigned keypad has an intuitive interface
with backlit display and provides:
menu-driven access to all system functions
default screen for quick view of system status
and set points
data reports to track performance and
efficiency
system diagnostics and alarm tracking for
troubleshooting
single-point multiple-humidifier control
without an additional system controller
password protection of setup parameters
wall-mounting with a standard telephone
plate, flush mounting, or hand-held options
Tank temperature sensor:
preheats tanks for uninterrupted operation
senses for freeze protection
senses for low water/over temperature
protection
Sensitivity to low-conductivity water
(important when using a standard
humidification system with low-mineral-content
water)
Uses Echelon’s LonTalk
®
, an open
communications protocol used by most major
control companies, allowing full interaction
with building management systems
Single-controller platform; modular design
The new VAPOR-LOGIC
3
controller will soon
be standard on all DRI-STEEM humidifiers.
The base configuration includes a main
controller board and keypad. Expansion
modules will increase capability, thereby
allowing all systems to use the same controller
platform and keypad interface.
Year-2000 compliant
Product overview
VAPOR-LOGIC
®
3
features overview.
Product overview:
Summary of features