4
VAPOR-LOGIC
®
3 main control board connections
J1 Wire terminal supplies 24 VAC to power the
VAPOR-LOGIC
3
control board.
• Double terminal T1 – 24 VAC, 10 VA
maximum load
• Triple terminal T2 – 24 VAC common
J2 RJ11 female modular jack connection for supply
voltage and FTT-10A communication to
keypad/display
J3 RJ45 female modular jack connection for FTT-
10A communication to LonTalk
®
network
J4 Wire terminal connection for FTT-10A
communication to LonTalk network. Terminals
A and B provide the communication lines. The
last terminal is earth ground.
J5 End of line communication terminator pins
J6 1/4" push-on connector for earth ground
J7 0-15 VDC analog output, typically connected to
the input of a steam or hot water valve.
Terminal 34 is the positive output signal and
terminal 35 is common.
J8 Connector receives necessary continuity input
signals from water detection devices:
• Probe system water level detection
– Terminal 30 detects maximum water level
from top probe rod and brown plug wire.
– Terminal 31 detects water level at refill
point from middle probe rod and orange
plug wire.
– Terminal 32 detects water level at its lowest
point from lower probe rod and purple plug
wire.
– Terminal 33 is the common return path for
all water detection rods from the humidifier
tank machine ground back to
VAPOR-LOGIC
3
control.
• DI/RO system detection
– Terminals 30 and 31 are not used.
– Terminal 32 is connected to the humidifier
tank low water float switch (normally
open).
– Terminal 33 is the return signal from the
float switch to VAPOR-LOGIC
3
control via
machine ground.
J10 Ribbon cable connector for VAPOR-LOGIC
3
expansion modules
More on next page ...
Product overview
Main control board connections.
Product overview:
Main control board connections