DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 63
• Clean the skim/overflow port
– Water should drain from the skimmer drain pipe after
each fill cycle. This should be verified visually by a weekly
inspection.
– Loosen deposits in and around the skimmer/overflow port
with a long tool such as a screwdriver.
– If flow through the water seal/P-trap is diminished due to
mineral accumulation:
• Remove the water seal piping from the humidifier and
flush out.
• Replace the water seal with new piping if the minerals
have hardened in the water seal.
• Clean low water cutout probe — Remove the shroud cover
and inspect the probe rod for mineral accumulation. The rod
is located on the top of the tank near the back. Use stainless
steel wool to clean the probe .
• Inspect blower motor — A lubrication port is not provided,
therefore lubrication is not required.
• Remove dust — Using a vacuum, remove all dust from areas
around the motor, vent fan(s), and louvers that allow air to
the shrouded area.
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s ( c o n t i n u e d )
Inspection and maintenance (continued)
I m p o r t a n t :
Minimum water supply pressure is 25 psi
(172 kPa).
More on next page ▶
W A R N I N G !
When performing maintenance on the GTS
humidifier, always change the control mode
to Standby, place all power disconnects in
OFF position and lock in OFF position, close
the field installed manual water supply and
gas shut-off valves. Failure to follow these
instructions may cause severe bodily injury
or death from electric shock.
Maintenance
mc_052908_0815-2