Page 16 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
O u t d o o r e n c l o s u r e m o u n t i n g
( c o n t i n u e d )
Figure 16-1:
GTS outdoor enclosure with standard or optional steam outlet, elevation view
Notes:
1. The outdoor enclosure has two available steam distribution configurations. The standard configuration has a steam outlet at the back of the outdoor enclosure
for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the outdoor enclosure and down
through the enclosure pipe chase into a building.
2. There are three knockouts located on the right and left side of the enclosure. Run the electrical power and gas piping into the enclosure at these knockouts.
3. Piping from the GTS unit to the steam outlet is stainless steel pipe. Piping from the steam outlet to the dispersion assembly is provided by the installer.
Choose interconnecting steam piping material that is appropriate for the application (e.g., for high-purity steam applications, consider using stainless steel
interconnecting steam piping). See Page 22 for steam outlet sizes.
4. The GTS housed in an outdoor enclosure will operate properly in operating temperature of –40 °F to 122 °F (–40 °C to 50 °C).
5. Install external flue piping shall be provided by installers and field installed. The flue of the outdoor enclosure exits out the left side of the unit and a vertical
stack must be constructed. The stack must be a minimum of 5–10 feet (1.5–3.0 m) above the top of the roof. However, the exact height varies depending
on unit size, climate, etc. Governing codes prevail. A UL or UL/CSA (or equivalent) listed cap must be used and a drip tee included. DRI-STEEM recommends
installing a high-wind vent cap on all GTS humidifiers.
Standard steam outlet Optional steam outlet
Flue piping (by others)
Ventilation fans
1½" (38 mm) knockouts
4" (102 mm) o.c.
Steam outlet
(See Note 1)
OM-1227M
GTS
humidifier
Steam outlet (See Note 1)
Combustion
air intake
Flue piping (by installer)
Ventilation fans
Power block
1½" (38 mm) knockouts
4" (102 mm) o.c.
Emergency
drain
Pipe chase
OM-1228M
GTS
humidifier
Power block
Emergency
drain
Pipe chase
Combustion
air intake
Installation