DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual Page 33
Never connect this humidifier to a chimney serving a fireplace,
unless the fireplace opening is permanently sealed off.
Code prohibits venting into an unlined masonry or concrete
chimney.
If this humidifier is connected to a lined, masonry chimney, the
chimney must be sized and installed according to the provisions
of the National Fuel Gas Code or Canadian CAN/CGA.B149
requirements, or governing codes.
Vent connector serving this appliance shall not be connected into
any portion of mechanical draft systems operating under positive
pressure.
Add insulation to any roof or wall penetration vent connector
that is exposed to ambient temperatures of 30 °F (0 °C) or
less, especially any application using single-wall vent pipe as a
connector.
Do not insulate vent pipe exposed to outdoor weather conditions
(e.g., above roof lines).
Install vent piping as direct as possible, with a minimum number
of turns or elbows.
Rigidly support the vent pipe every 5' (1.5 m) or less with hangers
or straps to ensure there is no movement after installation. The
humidifier vent box should not support the weight of the vent
piping.
No portion of the vent system should extend into, or pass through,
any circulation air duct or plenum.
• The vent system must terminate above the roof surface per the
National Fuel Gas Code, CAN/CGA.B149, or National Gas
Safety Code (Installation & Use) Regulations (latest revision)
requirements or governing codes, and must include a UL or
UL/CSA listed vent cap or roof assembly, unless prohibited by
governing codes. DRI-STEEM recommends installing a high-
wind vent cap on all GTS humidifiers.
For vertical vent pipe terminations only: This humidifier may be
commonly vented with other listed Category I gas-fired appliances.
Total input rates of all appliances determines the vent size.
Install and fire-stop all vent pipe passing through floors, ceilings,
and walls with the proper clearances from combustible material
according to the National Fuel Gas Code, Canadian Standards
CAN/CGA.B149, the National Gas Safety Code (Installation &
Use) Regulations (latest revision), or governing codes.
In replacement installation where an existing vent system may
be used, inspect the vent system for condition, size, type of
vent material, and height to meet the requirements in these
instructions. When connecting the humidifier to a gas vent or
chimney, the installation must be in accordance with Part 7,
Venting of Equipment, of the National Fuel Gas Code, ANSI
Z223.1; Section 7, Venting Systems and Air Supply Appliances, of
the CAN/CGA B149 Installation Codes; The National Gas Safety
Code (Installation & Use) Regulations (latest revision), governing
building codes, and the vent manufacturer’s instructions.
Ve r t i c a l a n d h o r i z o n t a l v e n t i n g
( c o n t i n u e d )
W A R N I N G !
For applications where the vent pipe
terminates in a vertical position, the
horizontal length of the vent and vent
connector must not exceed the height of
the vent system unless a power venter is
used. Failure to follow these instructions
could cause flue gases to exit the vent piping
causing severe personal injury or death.