DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual Page 35
D i s p e r s i o n : G e n e r a l i n s t r u c t i o n s
Selecting the dispersion assembly location
• For each dispersion device, DRI-STEEM documents distances
required for absorption to occur. If you have questions about
absorption distances, see the absorption tables in the U.S. English
version of the GTS catalog, available for viewing, printing, or
ordering at www.dristeem.com
• It is important that the dispersion assembly is positioned where
the water vapor being discharged is carried off with the airstream
and is absorbed before it can cause condensation or dripping in
the duct.
• In general, the dispersion assembly is best placed where the
air can most readily absorb the moisture being added without
causing condensation at or after the unit. This normally is after
the heating coil or where the air temperature is highest.
• Place the dispersion assembly so that absorption occurs before
the intake of a high efficiency filter. The filter can remove the
visible moisture and become waterlogged.
• Place the dispersion assembly so absorption occurs before coming
in contact with any metal surface.
• Place the dispersion assembly so absorption occurs before fire or
smoke detection devices.
• Place the dispersion assembly so absorption occurs before a split
in the duct. Otherwise, the dispersion assembly may direct more
moisture into one duct than the other.
• When draining dispersion condensate to an open drain, provide
a 1" (25 mm) gap between the condensate drain piping and the
drain. Locate air gap only in spaces with adequate temperature
and air movement to absorb flash steam; otherwise, condensing
on nearby surfaces may occur.
Where to find more information
On our Web site:
The following documents can be viewed,
printed or ordered from our web site,
www.dristeem.com
Catalogs (include dispersion nonwetting
distance graphs):
GTS
Ultra-sorb
Installation, Operation and Maintenance
manuals:
Ultra-sorb
Vapor-logic4 (includes sensor
placement recommendations and
troubleshooting information)
DRI-STEEM Design Guide
(includes steam
loss tables and general humidification
information)
In Dri-calc:
Dri-calc is our humidification system sizing
and selection software, which can be
ordered at www.dristeem.com.
Included in Dri-calc:
A comprehensive library of installation
guide documents, including:
Rapid-sorb installation instructions
for vertical airflows
Recommended dispersion placement
within a duct or air handler
Recommended sensor placement
Or call us at 800-328-4447
While obtaining documents from our Web
site or from Dri-calc is the quickest way to
review our literature, we will also mail to
you any literature you need.
Installation