P a g e 6 8 • D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e • P a g e 6 9
maximum lift of 2.5' (0.76 m). Do not attempt lifts in excess of 5'
(1.5 m).
• Steam trap. When lifting condensate, use an inverted bucket type
steam trap. Float and thermostatic (F&T) traps are more prone
to water hammer damage with a flooded trap, which may occur
when lifting condensate.
• Pipe size. The size of the vertical portion of the piping should be
" (DN15) pipe thread.
• Check valve (swing type). Install a low-pressure differential swing
check-valve adjacent to the trap. This will prevent backflow of
condensate into the humidifier during periods of little or no
steam pressure. Failure to do so could result in the accumulated
backflow discharging from the humidifier when steam pressure is
resumed. Spring type check-valves are not recommended as they
can reduce pressure available for condensate lifts.
Eliminating excess heat from pressurized steam-jacketed
humidifiers
In some applications with steam-jacketed humidifiers, the heat
given off by the steam-heated tube (not the sensible heat of the
steam) may be undesirable. While relatively insignificant in a single-
tube unit (usually a rise of less than 2 °F [1 °C]), it can be much
greater in a closely-spaced, multiple-tube installation. This can be
dealt with in several ways:
1. Manually turn off the steam supply valve during nonhumidifying
periods.
2. Insulate the tube exterior. (Note that this enlarges the tube
profile, causing additional resistance to airflow.)
3. Provide an automatic shut-off valve for the jacketing steam
circuit in addition to the modulating control valve. This
Humidier isolation valve
Modulating control valve
Figure 68-1:
Single humidifying steam path