P a g e 8 • D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e • P a g e 9
Economizer cycle method
Many year-round air conditioning systems use economizer
cycle control. Economizer cycles use cool outside air instead of
mechanical cooling to maintain building temperature when the
outside temperature is moderate (typically spring and fall).
Figure 8-1 shows a typical application where a mixed-air controller
positions a modulating damper motor, which adjusts the outside
air intake and return dampers. Note that the dampers are opposing
— as one moves toward open, the other moves toward closed, and
vice versa — to maintain a mixed air temperature of 55 °F as the
outside air temperature rises and falls.
When the outside air temperature rises to 55 °F (100% outside air),
the outside air damper returns to a minimum setting (usually about
10%) and mechanical cooling takes over. Table 9-1 shows how
outside air percentages change with varying outside and mixed air
temperatures.
As the outside temperature rises, the ratio of outside air to return
air increases. This works toward increasing the humidification load.
For example, to cool return air to 55 ˚F, you can admit 50%
outdoor air at 40 ˚F, but only 17% outdoor air at -20 ˚F (see Table
9-1). The warmer the outdoor air temperature, the more air volume
that can be admitted. More air volume means more air that needs
to be humidified, thereby increasing the humidification load
required to maintain RH set point.
To better understand how varying temperatures and air volumes
affect humidification load calculations, review the following
formulas, sample problems, and tables.
The formula for determining the quantity of outside air in an
economizer cycle is:
V
2
= V
AH
/ [(A/B) + 1]
Where:
V
AH =
V
1 +
V
2
V
1
= Volume (cfm) of return air
V
2
= Volume (cfm) of outside air
A = Temperature difference between mixed air
and outside air
B = Temperature difference between return
air and mixed air
Outside air
Return air
Mixed air
55
˚
F
Mixed air controller
set at 55 ˚F
Damper
arms
Damper motor
Damper
Figure 8-1:
Typical economizer control system