Table 22-1:
Steam loss of interconnecting vapor hose, tubing, and pipe
Description
Nominal hose,
tubing, or pipe size
Steam loss
Insulation thickness
Noninsulated Insulated
inches DN lbs/hr/ft kg/h/m lbs/hr/ft kg/h/m inches mm
Hose
1 40 0.15 0.22 N/A N/A N/A N/A
2 50 0.20 0.30 N/A N/A N/A N/A
Tubing
1 40 0.11 0.16 0.020 0.030 2.0 50
2 50 0.14 0.21 0.025 0.037 2.0 50
3 80 0.20 0.30 0.030 0.045 2.5 64
4 100 0.26 0.39 0.030 0.045 3.0 76
5 125 0.31 0.46 0.035 0.052 3.0 76
6 150 0.36 0.54 0.039 0.058 3.0 76
Pipe
1 40 0.22 0.33 0.020 0.030 2.0 50
2 50 0.25 0.38 0.025 0.037 2.0 50
3 80 0.39 0.58 0.030 0.045 2.5 64
4 100 0.49 0.73 0.030 0.045 3.0 76
5 125 0.59 0.88 0.035 0.052 3.0 76
6 150 0.70 1.04 0.039 0.058 3.0 76
Note: Data based on ambient air temperature of 80 °F (26.7 °C), berglass insulation, copper tubing, and Schedule 40 pipe.