P a g e 4 4 D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e P a g e 4 5
Figure 45-1:
Standard water systems
Systems using tap or softened water control water
levels electronically using a three-rod probe. The
controller responds with the above actions when the
water level reaches each rod.
Fill valve closes
Fill valve opens
Low-water cutoff
Figure 45-2:
DI/RO water systems
Evaporative system water level control
Standard water systems require conductive water
DRI-STEEM’s standard water evaporating chambers (found in
DRI-STEEM evaporative humidifiers with model numbers that do
not end in “DI”) require fill (makeup) water to have conductivity
of at least 100 µS/cm (2 grains/gallon). These systems use a
conductivity probe to measure water levels and, therefore, will
not operate with DI/RO water (which is demineralized and not
conductive).
Important note about chloride corrosion
Corrosion can occur in evaporating chambers when chloride levels
are unusually high in the supply water. This is usually caused
by improperly maintained DI treatment beds, but has occurred
with potable water supplies. If you see stainless steel pitting, call
DRI-STEEM technical support.
Fill valve
Float rod
Float ball