P a g e 3 8 D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e P a g e 3 9
Table 38-1:
How fill water type affects performance, maintenance, steam quality, and efficiency in isothermal humidification
systems
Fill
water type/
conductivity
Skimming
required?
(Y/N)
Drain/ush
frequency
Hardness
RH
performance
(control range)
Maintenance
requirements
Humidication
steam quality
Water and
energy
efciency
Potable
(minimum
conductivity
100 µS/cm)
Y System with a
manual drain:
Humidier typically
drains one time
per season, but
may need to
increase drain and
ush frequency
based on quarterly
inspections,
especially with
water over 12 gpg
(205 mg/L).
2-35 gpg
(35-600 mg/L)
±3% of set point
with service
interrupted by
draining and
ushing
If water is harder
than 12 gpg
(205 mg/L), scale
buildup occurs
quickly. Increasing
skim and drain/ush
cycles helps reduce
scale, as does regular
cleaning. The key
is to skim or ush
minerals while they
are still in solution
and before they
attach to humidier
components as scale.
As pure as the ll
water. Dissolved
solids may transfer
to the airstream with
humidity vapor.
As water hardness
increases so does the
need for skimming
and draining, thus
increasing water
and energy usage,
for makeup water
replacing water
lost to skim and
ll cycles must be
heated. In addition,
performance
degradation can
occur in heat
exchanger-based
systems if the heat
exchanger becomes
coated with mineral
scale.
Potable
(minimum
conductivity
100 µS/cm)
Y System with auto
drain and ush:
Several times per
season.
2-35 gpg
(35-600 mg/L)
±3% of set point
with service
interrupted by
draining and
ushing
Softened
(minimum
conductivity
100 µS/cm)
Y System with a
manual drain:
Humidier typically
drains one time
per season, but
may need to
increase drain and
ush frequency
based on quarterly
inspections.
2-12 gpg
(35-205 mg/L)
±3% of set point
with no service
interruption
Can go up to two
years without
cleaning, but
quarterly inspections
are encouraged
to verify softener
operation. Drain,
ush and skim
frequency/duration
affect maintenance
requirements.
As pure as the ll
water. Dissolved
solids may transfer
to the airstream with
humidity vapor.
As water hardness
increases so does the
need for skimming
and draining, thus
increasing water
and energy usage,
for makeup water
replacing water lost
to skim and ll cycles
must be heated.
Softened
(minimum
conductivity
100 µS/cm)
Y System with auto
drain and ush:
Several times per
season.
2-12 gpg
(35-205 mg/L)
±3% of set point
with no service
interruption
High purity
(DI/RO)
N Typically need to
drain one time per
season.
0-2 gpg
(0-35 mg/L)
±1% of set point Cleaning typically
not required, but
quarterly inspections
are encouraged
to verify ltration
operation.
Pure humidication
steam. Steam
generated by an
isothermal process
is more pure than
humidication
produced by an
adiabatic process.
Efcient, because
there is no water
used for skimming
or drain/ush cycles.
However, a very
small amount of
water regularly
overows to keep
the P-trap lled.
Boiler steam
(direct
injection)
N/A N/A N/A ±1% of set point Yearly inspection.
Typically, no other
regular maintenance
is required.
Efcient, because an
existing boiler can
be used.