P a g e 3 0 • D R I - S T E E M D e s i g n G u i d e
D R I - S T E E M D e s i g n G u i d e • P a g e 3 1
Choose energy source wisely
A pound of water requires approximately 1,000 BTUs to vaporize.
Given that proper humidification typically requires vaporizing
two to three pounds of water for every 100 cfm of outside air
introduced into the system, humidification energy use ranges from
2,000 to 3,000 BTUs per 100 cfm of outside air.
A kilogram of water requires approximately 2.4 kJ to vaporize.
Given that proper humidification typically requires vaporizing
1.5 to 2.5 kilograms of water for every 100 m
3
/h of outside air
introduced into the system, humidification energy use ranges from
3.5 kJ to 5.8 kJ per 100 m
3
/h of outside air.
Two major types of humidifiers
• Isothermal systems use heat from an external source to create
humidity. Electricity, natural gas, hot water, and boiler steam
are isothermal heat sources used to boil water into steam for
humidification.
The table on Page 32 shows DRI-STEEM’s isothermal humidifiers
described by energy type.
• Adiabatic systems use heat from the surrounding air to change
water into vapor for humidification (evaporation). Foggers,
ultrasonic, and pezio disk humidifiers are typical adiabatic
systems.
Why choose isothermal humidification?
• Choose isothermal humidification if you require predictable,
controllable, and short absorption distances. Adiabatic systems
require long absorption distances and often do not provide
complete absorption in typical HVAC applications.
• Choose isothermal humidification if you have low air
temperatures in your ducts. Adiabatic humidification requires
very warm or preheated air for absorption to occur.
• Choose isothermal humidification if there is an on-site boiler
or hot water source. Direct steam injection or a heat-exchanger
type isothermal system may be most appropriate. Consider
DRI-STEEM’s:
– Steam injection humidifiers: ULTRA-SORB, MAXI-BANK,
Multiple-Tube, MINI-BANK, Single-Tube, or AREA-TYPE
– STS Steam-to-Steam (with heat exchanger) evaporative steam
humidifier
– LTS Liquid-to-Steam (with heat exchanger) evaporative steam
humidifier
See also the text at left for more detail about choices when using
on-site steam.
S e l e c t e n e r g y s o u r c e
Choices when using on-site steam
Using on-site steam for humidification can
be a good economic choice. Pressurized
steam can be injected directly into the
airstream, or passed through a heat
exchanger to heat potable, softened, or
DI/RO water for humidification steam.
Chemically-treated boiler steam may affect
indoor air quality. Many humidifier users
are finding that chemically treated, boiler-
generated steam is unsuitable for direct
injection humidification. This is because
boiler water is treated with anticorrosion
chemicals that are then emitted with the
steam into the occupied space. These
chemicals can irritate eyes and skin and
aggravate respiratory disorders such as
asthma. In addition, they can accelerate the
aging process of certain materials like paper
and wood, an issue especially relevant to
museums.
When designing your humidification system
using boiler steam, consider a closed loop
system such as DRI-STEEM’S STS Steam-to-
Steam humidifier to prevent the discharge of
chemically treated steam into your building.
Comentarios a estos manuales