TROUBLE-SHOOTING GUIDE
PROBLEM POSSIBLE CAUSE RECOMMENDED ACTION
HUMIDITY BELOW
DESIRED LEVEL
Unit operating but fails to meet
required humidity output
Unit undersized; replace with a larger unit or add
additional humidifier.
Skimmer rate is too high.
If drain valve will not close fully, determine the cause
and clean, repair or replace as needed.
If drain pipe water seal is allowing steam to go down
the drain, repair as needed.
If there is an improper water seal height, increase to
recommended height. (See humidifier O&M manual)
If there is excessive internal steam pressure,
determine the cause of the high pressure (i.e.: high
duct static pressure, undersized orifices in dispersion
tubes, water, or crushed vapor hose, etc.) and repair
as required.
Replace leaking gasket or vapor hose.
Recalibrate if controls are out of calibration.
If fill valve is stuck open, repair or replace.
If zone valve will not open, repair or replace.
No call for humidity from
humidistat or control and high
limit humidity transmitters
Low or no signal strength from humidistat.
Check for proper wiring.
Check humidity transmitters. (4-20 mA output)
Adjust set point if VAPOR-LOGIC set point is too low.
Heating elements not operating If heaters are burned out, refer to previous section on
HEATER BURNOUT.
Humidistat calling for humidity (out of calibration)
Check for control voltage if limit controls (air flow
proving switch, zone valves, etc.) are not allowing unit
to operate.
Check fuses and replace if they are blown.
Check if the (optional) heater overtemperature has
been tripped. Reset if necessary.
Excessive outside air volume Verify proper operation of fans, dampers, VAV
systems, etc.
®