VAPOR-LOGIC also has the capability of being the
primary humidity controller when a humidity duct or
room transmitter is furnished. The digital key pad
display module allows you to monitor actual set point
and to change desired set point when necessary.
The time proportioning function operates when actual
% RH is within the throttling range. When the actual %
RH falls below set point and out of throttling range
100% output demand is necessary. If the actual % RH
increases above and out of throttling range, humidifier
turns off completely. See figure 27-1.
DRI-STEEM Offers Five Forms of Time
Proportioning:
• TP Modulation for single electrical output humidifiers
• TP/Sequencer Modulation for multiple electrical
output humidifiers
• SCR/Sequencer Modulation using solid state power
controller with sequence of multiple electrical
humidifier outputs
• 100% SCR Modulation is total modulation of all the
electrical outputs together through a SCR power
control system without sequencing
• Varying 6-9 VDC or 1-10 VDC analog signals to
modulate steam or hot water valves
VAPOR-LOGIC
®
CONTROL SCHEMES
Figure 27-1: VAPOR-LOGIC Time Proportioned Controller
Throttling Range 5% RH
(symmetrical around Set-
point)
100% Demand
Desired
Set-point
52.5
50
47.5
Actual % RH
0% Demand
Time
Humidity % RH
Throttling Range
Set Point: 50% RH
Throttling Range: 50%
RH
OM-590