FAULT INDICATOR CODES
FAULT
MASTER
(CODE)
SLAVE 1
(CODE)
SLAVE 2
(CODE)
SLAVE 3
(CODE)
DIGITAL DISPLAY READ-OUT
EEPROM
FAILURE
SSSSL LSSSL SLSSL LLSSL "17) MASTER EEPROM" (Master control
board programming failure)
"18) SLAVE 1 EEPROM" (System B
control board programming failure)
"19) SLAVE 2 EEPROM" (System C
control board programming failure)
"20) SLAVE 3 EEPROM" (System D
control board programming failure)
TRANSMITTER
FAULT (Control)
LSLSL none none none "22) RH XMTR" (Control % RH humidity
transmitter failure)
HUMIDISTAT OR
SIGNAL BY
OTHERS (Fault)
LSLSL none none none "22) RH STAT" (Humidistat or signal
failure)
INPUT SIGNAL
FAULT
LSLSL none none none "RH OUT OF RANGE"
TRANSMITTER
FAULT (High limit)
SLLSL none none none "23) HL XMTR" (Control duct high limit %
RH humidity transmitter failure)
TRANSMITTER
FAULT
(temperature)
LLLSL none none none "24) TMP XMTR" (Temperature
compensation transmitter failure)
PROBE FAULT SSSLL none none none "25) PROBE FAULT" (Water detection
probe defective)
LOCAL DIGITAL
DISPLAY FAULT
SSSSS none none none "1) LOCAL DISPLAY" (Communication
failure to Local Digital Key Pad)
REMOTE DIGITAL
DISPLAY FAULT
SSLSL none none none "21) REMOTE DISPLAY" (Communication
failure to Remote Digital Key Pad)