FAULT
MASTER
(CODE)
SLAVE 1
(CODE)
SLAVE 2
(CODE)
SLAVE 3
(CODE)
DIGITAL DISPLAY READ-OUT
COMMUNICA-
TION FAILURE
SSSSS LSSSS SLSSS LLSSS "1) LOCAL COMM" (Master to local key
pad communication failure)
"21) REMOTE COMM" (Master to remote
key pad communication failure)
"2) SLAVE 1 COMM" (System B control
board to Master control board failure)
"3) SLAVE 2 COMM" (System C control
board to Master control board failure)
"4) SLAVE 3 COMM" (System D control
board to Master control board failure)
LEVEL CONTROL
(PROBE
FAILURE)
SSLSS LSLSS SLLSS LLLSS "5) MASTER WATER" (Main humidifier
probe and low water failure)
"6) SLAVE 1 WATER" (System B
humidifier probe and low water failure)
"7) SLAVE 2 WATER" (System C
humidifier probe and low water failure)
"8) SLAVE 3 WATER" (System D
humidifier probe and low water failure)
DRAIN VALVE
FAILURE
SSSLS LSSLS SLSLS LLSLS "9) MASTER DRAIN" (Main humidifier
water drain failure)
"10) SLAVE 1 DRAIN" (System B
humidifier water drain failure)
"11) SLAVE 2 DRAIN" (System C
humidifier water drain failure)
"12) SLAVE 3 DRAIN" (System D
humidifier water drain failure)
FILL VALVE
FAILURE
SSLLS LSLLS SLLLS LLLLS "13) MASTER FILL" (Main humidifier
water fill failure)
"14) SLAVE 1 FILL" (System B humidifier
water fill failure)
"15) SLAVE 2 FILL" (System C humidifier
water fill failure)
"16) SLAVE 3 FILL" (System D humidifier
water fill failure)
FAULT INDICATOR CODES