If you are experiencing a problem with starting up your
system, please refer to the following:
1. Verify that wiring is done per instructions in
this manual and the unit wiring diagram.
2. Make sure key pad is not inside of the control
cabinet.
3. Check water level control voltages; the
reading should be 2.5 VAC without water, 0
VAC with water from ground (pin 4-J12) to
probe inputs (pins 1, 2 & 3-J12).
4. Check the throttling range on the Main Menu
of the keypad (default is 11%).
5. Check cycle setting on the Main Menu of the
keypad (default is 60 seconds; default is 4
seconds with SCR).
6. Check delay setting on the Main Menu of the
keypad (default is 20 seconds).
7. Check time to auto drain (default is 50 hours).
8. Check drain duration (default is 8 minutes).
9. Check drain and flush sequence (default is 8
minutes).
10. Check RH setting.
11. Check control signal.
12. Perform test cycle of the system.
13. Check amp draw of heater(s); refer to wiring
diagram for proper rating.
If you are still experiencing difficulties, have the above
information available with the model number(s) of the
humidifier, the VAPOR-LOGIC
®
program code, the
VAPOR-LOGIC board revision, and the
VAPOR-LOGIC software revision and call DRI-STEEM
for help.
Note: Your humidification system may not have all
of the options listed above. If an item does not
appear, skip to the next item and continue the
process.
START-UP TROUBLE-SHOOTING CHECK LIST