DRI-STEEM Vapor-logic3 to Vapor-logic4 Adaptor Board Installation Manual • Page 19
Start-up
See the Start-up commissioning checklist in the humidifier’s
Installation, Operation, and Maintenance Manual. Before resuming
operation, verify that the current humidifier configuration matches
the Vapor-logic4 controller configuration. Refer to the Vapor-logic4
Installation and Operation Manual, and validate every parameter in the
Vapor-logic4 Setup menu.
When resuming operation, do not leave the humidifier unattended;
allow it to cycle through multiple fill cycles to verify that the
humidification system is functioning properly.
Test outputs
When completing an installation or repair, cycle all outputs, such as
fill valve, drain valve, etc., to verify operation. Go to the test outputs
section of the Diagnostics menu and scroll through each connected
output to verify operation. During testing, the humidifier mode
changes to Standby and the tank status changes to Test.
Test run
Vapor-logic4 has a test run capability to confirm system functionality.
This capability allows a technician to simulate a demand for steam
production when there isn’t one (such as when performing routine
maintenance). To confirm functionality, go to the test run section of
the Diagnostics menu. Set system demand percent and set test run time
duration. During testing, the humidifier mode changes to Standby and
the tank status changes to Test.
mc_102108_1350
All Humidifiers:
Start-up and validation
Figure 19-1:
Field conversion label
When the upgrade is complete, ll out the Field
Conversion Label included with the upgrade kit, and
install it on the humidifier subpanel near the unit label.
Humidifier De-scaling Solution
Scale buildup on humidifier heaters and heat
exchangers acts as an insulator, reducing
humidifier performance while increasing
energy costs. To keep humidifiers operating
as efficiently as possible, remove scale with
DRI-STEEM's Humidifier De-scaling Solution,
available for purchase from your DRI-STEEM
representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DRI-STEEM's Humidifier De-scaling Solution
is the only approved cleaner/de-scaler for use
with DRI-STEEM humidifiers. Use of other
cleaners/de-scalers may void your DRI-STEEM
warranty.