DRI-STEEM Vapor-logic3 to Vapor-logic4 Adaptor Board Installation Manual • Page 15
Electric humidifiers:
Safety circuit wiring
Figure 15-2:
Vaporstream or CRUV with door interlock; Vaporstream with door interlock and/or cover interlock
• CRUV with door interlock
• Vaporstream with door interlock
• Vaporstream with door interlock and/or cover interlock
The following procedure leaves the safety circuit (door interlock and
low water) wired in series with one alarm:
1. Make sure gray-handled jumper supplied with upgrade kit is
inserted into terminals P3-3 and P3-4 on Vapor-logic4 adaptor
board (Figure 15-1).
2. Vaporstream only: Locate wire 801 that runs to expansion board
terminal T1 (Figure 15-2), and land it at terminal P3-3 on
Vapor-logic4 adaptor board. If wire 801 does not reach P3-3, use
a longer 18-gauge, stranded wire. Torque terminal block screws to
2.5 in-lb (0.28 N·m)
Proceed to “Start-up and validation” on Page 19.
VL3 main board VL3 expansion board (Vaporstream only)
VL4 adaptor board VL4 adaptor board
DM-11262
DM-11259
24 VAC
801
h
T1
24 VAC
801
LW
P3
P3-3
P3-4
FPsw
h
Gray-handled
jumper provided
with upgrade kit
Figure 15-1:
Leaving safety circuit wired in series
with one alarm
DM-10097
DM-10098
VL3 expansion board (Vaporstream only)
VL4 adaptor board
Comentarios a estos manuales