DriSteem Vapor-logic3 Manual de instalación Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 22
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
Page 18 DRI-STEEM Vapor-logic3 to Vapor-logic4 Adaptor Board Installation Manual
STS humidifiers
Keypad/display removal and replacement
The Vapor-logic3 keypad/display will not be re-used after this upgrade.
STS with mounted keypad/display
1. Push keypad/display straight up to disengage its mounting keyhole
slots, and pull it off of mounting plate.
2. Disconnect cable from the Vapor-logic3 keypad/display.
3. Plug cable into new Vapor-logic4 keypad/display, and mount new
keypad/display.
4. Close and tightly secure control cabinet door.
STS with unmounted keypad/display
1. Disconnect cable from Vapor-logic3 keypad/display.
2. Plug the cable into new Vapor-logic4 keypad/display.
Safety circuit wiring
The following procedure leaves the safety circuit (door interlock) wired
in series with one alarm See Figure 18-1.
1. Locate wire 801, and land it at terminal P4-1 on Vapor-logic4
adaptor board. If wire 801 does not reach P4-1, use a longer
18-gauge, stranded wire.
2. Torque terminal block screws to 2.5 in-lb (0.28 N·m).
Proceed to “Start-up and validation” on Page 19.
801
P4
1
24 VAC
h
l s w
4 3 2
TTA12
Figure 18-1:
Leaving safety circuit wired in series
with one alarm
P4-1
VL4 adaptor board
Vista de pagina 19