1BHFt%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBM
4UFQo4FUVQ
Table 30-1:
Setup menu (continued)
Menu item
Default
value
Minimum
value
Maximum
value
Units Notes
Remote temp sensor
(not an XT menu item)
Changing temperature sensor settings can require
component changes for system to operate correctly.
Temp compensation -- -- -- --
Temp comp enabled -- No Yes --
Temp monitor -- -- -- --
Temp monitor enabled -- No Yes --
Temp sensor offset -- -- -- --
Used to calibrate temperature monitoring sensor and
temperature compensation sensor
Temp sensor offset
0 -20 20 °F
0 -11 11 °C
Communications
Changing communications settings can require
component changes for system to operate correctly.
BACnet -- -- -- --
Unlock code 0 0 999999 --
BACnet enabled -- No Yes --
BACnet comm channel 19200MS/TP BACnet IP 76800 MS/TP --
Device instance 255 0 4194303 --
MS/TP station 1 0 127 -- MS/TP only
Max masters 127 0 127 -- MS/TP only
UDP port (47808) 47808 1024 65535 -- BACnet/IP only
Modbus -- -- -- --
Modbus enabled -- No Yes --
Modbus baud rate 9600 4800 38400 --
Modbus address 99 0 255 --
LonTalk -- -- -- --
LonTalk enabled -- No Yes --
Network IP address --------
Network IP address 192.168.1.195 0.0.0.0
255.255.
255.255
--
Network IP mask 255.255.255.0 0.0.0.0
255.255
255.255
Enable DHCP No No Yes --
Use keypad/display to access this menu item. This item
is not available when using the Web interface.
Continued