4UFQo4FUVQ
Table 30-1:
Setup menu
Menu item Default value
Minimum
value
Maximum
value
Units Notes
Note: Your system might not have all of the items listed in this table (Pages 30 through 36).
Input signal
RH transmitter -- -- -- --
Transmitter enabled -- No Yes --
RH set point 35 0 100 %
RH offset 0 -20 20 %
DRI-STEEM recommends using default values for offsets
and PID settings when first setting up your humidifier.
PID tuning -- -- -- --
RH PID band 10 0 50 %
Proportional gain 80 0 1000 ---
Integral gain 40 0 1000 ---
Derivative gain 0 0 1000 ---
Dew pt transmitter -- -- -- --
Transmitter enabled -- No Yes --
Dew point set point
50 20 80 °F
10 -6 26 °C
Dew point offset
0 -20 20 °F
DRI-STEEM recommends using default values for offsets
and PID settings when first setting up your humidifier.
0 -11 11 °C
Dew point minimum 0 -100 Maximum °F /°C
Dew point maximum 100 Minimum 100 °F /°C
PID tuning -- -- -- --
Dew point PID band
10 1 20 °F
5120°C
Proportional gain 80 0 1000 --
Integral gain 40 0 1000 --
Derivative gain 0 0 1000 --
Demand signal -- -- -- --
VDC signal -- -- -- --
VDC signal enabled -- No Yes --
0% output at 1.0 0.0 Maximum VDC
100% output at 9.0 Minimum 10.0 VDC
mA signal -- -- -- --
mA signal enabled -- No Yes --
0% output at 4.0 0.0 Maximum mA
100% output at 20.0 Minimum 20.0 mA
Control via Modbus -- -- -- --
Choose Modbus, BACnet, or LonTalk in this section only
if your demand input signal is via Modbus, BACnet, or
LonTalk. If you are interoperating (sharing operating
parameters with a building automation system) using
Modbus, BACnet, or LonTalk protocols, see also the
Communications Setup options.
Modbus controlled No No Yes --
Control via BACnet -- -- -- --
BACnet controlled No No Yes --
Control via LonTalk -- -- -- --
LonTalk controlled No No Yes --
Continued