D R I - S T E E M V a p o r m i s t h u m i d i f i e r P a g e 1 5
Va p o r m i s t p i p i n g ,
D I / R O w a t e r m o d e l s
Figure 15-1:
Vapormist-DI (deionized/reverse osmosis water models) field piping overview
Two keyholes for wall mounting,
16" (406 mm) on center
Unions by installer
Strainer,
by installer
¾" pipe thread
(DN20) tank drain,
and P-trap piping,
rated for 212 °F
(100 °C). If piping
run is over 10'
(3 m) increase pipe
to 1¼" (DN32)
after P-trap.
1" (25 mm)
air gap
Spill funnel. Plumb
to floor drain
Frame drain
Cover
Install plumb
DC-1139
First 3' (1 m) of
water supply line is
recommended to be
stainless steel tubing with
a 2" (50 mm) water seal
or loop in the supply line
to isolate steam from
nonmetallic supply piping.
2" (50 mm)
12" (300 mm)
Notes:
Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.
Dashed lines indicate provided by installer.
The water supply inlet is more than 1" (25 mm) above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing codes prevail.
Install a union in the water supply and drain lines as shown to allow tank removal.
Damage caused by chloride corrosion is not covered by our DRI-STEEM warranty.
See the previous page for recommended piping for Vapormist standard water models.
See the dispersion section of this manual for more information about piping that connects the humidifier to the dispersion assembly.
Open drain required. See
first note below.
¾" pipe thread (DN20)
frame drain and
P-trap piping, rated
for 212 °F (100 °C)
Electrical conduit
knockouts provided
top and bottom:
Combination, for
½" and ¾" conduit
connectors (knock-
out diameters 22.3
mm and 28.6 mm)
Combination, for
¾" and 1" conduit
connectors (knock-
out diameters 28.6
mm and 34.9 mm)
Water supply line; water pressure must
be between 25 psi and 80 psi (175 kPa
and 550 kPa)
Steam vapor hose (maximum
run 10' [3 m]). May also use pipe
or tubing. See the DRI-STEEM
Design Guide for maximum pipe
or tubing lengths.