D R I - S T E E M V a p o r m i s t h u m i d i f i e r • P a g e 1 1
Va p o r m i s t s p e c i f i c a t i o n s
Table 11-2:
Space Distribution Unit specifications**
SDU
model
Maximum
capacity
Shipping
weight
Amps at
120V
(50/60 Hz)
Horse-
power
cfm m
3
/s dB*
lbs/hr kg/h lbs kg
SDU-E 102 46.3 61 28 2.07 1/8 545 0.26 64
SDU-I 30 13.6 68 31 3.20 1/5 760 0.36 58
Notes:
* Measurement taken 6.5' (2 m) in front of SDU cabinet.
** For visible vapor to be absorbed completely within the SDU-I unit before being
discharged as humidified air, room air must be 45% RH or less. Trying to maintain
greater than 45% RH will cause visible vapor and potential for moisture collection
on the discharge grille.
Notes about SDUs (Space Distribution
Units):
• The SDU-I is available for models VM-2
through VM-8, and all VM-10 models
except those using 240V, three-phase
power with SSR control.
• The SDU-E is available for all Vapormist
models except those models using
240V/480V/600V/three-phase power with
the SSR control option and drawing more
than 21.7 amps.
• SDUs ship separately from the Vapormist.
Table 11-1:
Vapormist specifications, capacities, and weights
Model
Maximum steam
capacity
Current draw (amps) Weights ‡
Single-phase Three-phase Shipping Operating
kW lbs/hr kg/h 120V 208V* 240V* 480V† 600V† 208V* 240V† 480V† 600V† lbs kg lbs kg
2 6 2.7 16.7 9.6 8.3 4.2 3.3 — — — — 80 36 95 43
4 12 5.4 33.3 19.2 16.7 8.3 6.7 16.7** 14.4** 7.2** 5.8** 80 36 95 43
6 18 8.2 — 28.8 25.0 12.5 10.0 25.0** 21.7** 10.8** 8.7** 88 40 122 55
8 24 10.9 — 38.5 33.3 16.7 13.3 33.3** 28.9** 14.4** 11.5** 88 40 122 55
10 30 13.6 — — 41.7 20.8 16.7 29.1** 25.3** 12.6** 10.1** 93 42 139 63
12 36 16.3 — — — 25.0 20.0 33.3 28.9 14.4 11.5 93 42 139 63
14 42 19.1 — — — 29.2 23.3 38.9 33.7 16.8 13.5 93 42 139 63
16 48 21.8 — — — 33.3 26.7 44.4 38.5 19.2 15.4 93 42 139 63
21 63 28.6 — — — 43.8 35.0 — — 25.3 20.2 95 43 152 69
25 75 34.0 — — — — 41.7 — — 30.1 24.1 95 43 152 69
30 90 40.9 — — — — — — — 36.1 28.9 101 46 156 71
34 102 46.3 — — — — — — — 40.9 32.7 101 46 156 71
Notes:
* On 208V/240V/single-phase/three-wire and on 208V/three-phase/four-wire supplies, the neutral line provides a separate 120V circuit for the SDU fan unit.
** For wire sizing, the highest leg draw is shown due to current imbalance.
† Add the following to Vapormist weights if using an SDU option (these weights are for additional control components housed within the Vapormist cabinet):
– SDU-I: 12 lbs (5.5 kg)
– SDU-E: 9 lbs (4 kg)
See the SDU weights Table 11-2 below for SDU weights (shipped separately).
‡ Add the following if using the SSR option:
– For single-phase or three-phase models drawing less than 21.7 amps, add 2 lbs (1 kg)
– For three-phase models drawing more than 21.7 amps, add 4 lbs (2 kg)
All Vapormists operate at 50/60 Hz.