DRI-STEEM Vapormist humidifier • Page 15
Table 15-1:
Ultra-sorb tube spacing and capacity
Tube spacing Maximum capacity
inches mm lbs/hr/ft
2
kg/h/m
2
3 76 36 175
6 152 18 88
9 229 12 59
12 305 9 44
Note:
The above steam flow capacity data are based on pounds (kg) of steam per hour per square
foot (meter) of face area, exclusive of headers, at various tube spacings.
mc_042710_0905
Dispersion: Ultra-sorb
Note:
The above data apply to all air velocities up to 1,500 fpm (7.6 m/s), and are based on air leaving the zone of humidification at conditions of 55 °F (13 °C) and
the stated % RH. The blue lines in the graph refer to the sample exercise described on Page 14.
Figure 15-1:
Ultra-sorb non-wetting distances
3"
6"
9"
12"
mc_042710_0900